Technology

The technology behind NICPL data centers

Every NICPL site — campus or containerized — is built on the same underlying direction: cooling matched to rack density, power designed for renewable-first resilience, and monitoring that treats every site as part of one network, all certified to the same Tier 3, TIA-942 standard. This page covers where that direction comes from; see TIA-942 vs Uptime for how our certification compares, or the FAQs for quick answers.

Our technology direction

Rather than a single fixed design repeated everywhere, NICPL provisions technology to match what a site actually needs — then holds every site to the same standard regardless of scale. Rack density is zoned per hall rather than fixed facility-wide, from air-cooled 5kW racks to hybrid-cooled 135kW racks, so density gets built where the demand is instead of over-building for a worst case.

Cooling across every design — campus or containerized — is air-cooled or closed-loop liquid-cooled only: no evaporative towers, no water-based heat rejection, so cooling consumes zero process water at any density, on any site. That shows up directly in Water Usage Effectiveness (WUE): evaporative-cooled facilities average around 1.9 L/kWh, while NICPL's zero-evaporative design targets below 0.05 L/kWh — see Campus Design for the full comparison. Power is built to the same rigor a TIA-942 Rated-3 design demands at every scale, and renewable supply is designed in from Day 1, not retrofitted later. Halls are also built to OCP Ready™ v1 Data Center Site criteria, so open, vendor-neutral rack and hardware designs — including GPU-dense AI configurations — drop in without facility rework. And every building, not just the data hall, targets IGBC Gold certification or better.

None of that is worth much without knowing it's actually holding — so every hall runs a hardwired IIoT sensor layer covering temperature, humidity, differential pressure, airflow, water leaks, vibration, door access, and air quality, feeding straight into the same unified DCIM + EMS platform rather than a patchwork of disconnected point tools. See Campus Design for the full sensor breakdown.

That direction plays out differently depending on what a site needs to do: a large, phased campus platform for sustained regional capacity, or a factory-built containerized unit for compute that needs to be live in weeks. Both are detailed below.

Two designs, one standard

5MW/20MW Campus Design

The primary platform: a standardized 5MW block that scales in place to a 20MW Tier-3 campus — cooling zoned by rack density, grid-tie power built to TIA-942 rigor, and unified monitoring across every site.

Explore the campus design →

Containerized Edge Data Centers

The fast, small-footprint line: factory-built 20ft/40ft units, including the 20ft/60kW instant-edge configuration, for sites that need compute in weeks rather than a full campus build.

Explore the containerized design →

Technical Glossary

Cooling

Air-cooled racks
Standard rack cooling via facility CRAC/CRAH air handling — the base technology for the 5kW–25kW density band.
In-row RDHx (Rear-Door Heat Exchanger)
A cooling coil mounted on the rear of the rack that removes heat from exhaust air in place, extending air-cooling headroom toward the top of the 5kW–25kW band without a room-level chilled-water retrofit.
Zero water-wastage cooling
NICPL cooling design deliberately excludes evaporative towers and other water-based heat rejection — air-cooled and closed-loop liquid cooling across every density band, so no process water is consumed or wasted for cooling at any site.
Free cooling
Using favourable outside air conditions to reject heat without running compressors — an air-side technique, consistent with NICPL's zero water-wastage cooling design.
Hot-aisle containment
Physically separating hot exhaust air from cold supply air to raise cooling efficiency.
Hybrid cooling
Cooling technology matched to rack density on a per-requirement basis across the 25kW–135kW band — direct-to-chip, liquid, or immersion, selected for the workload rather than one-size-fits-all.
Direct-to-chip cooling
Coolant delivered directly to a cold plate mounted on the processor or accelerator, removing heat at the source for the highest-density compute in the 25kW–135kW band.
Liquid cooling
Closed-loop liquid delivered to a cooling distribution unit (CDU) at the rack, used across the 25kW–135kW hybrid-cooling band alongside direct-to-chip and immersion options.
Immersion cooling
Full or partial submersion of IT hardware in a dielectric fluid; provisioned for Built-to-Suit deployments at the top of the 135kW density range.
PUE (Power Usage Effectiveness)
Ratio of total facility power to IT equipment power — the industry's core efficiency metric.
WUE (Water Usage Effectiveness)
Liters of water consumed per kWh of IT energy delivered, counting only water that leaves the site via evaporation or discharge. Industry average sits near 1.9 L/kWh; zero-evaporative designs like NICPL's target below 0.05 L/kWh.

Power & Electrical

N+1 redundancy
One more unit than the minimum needed, so a single failure doesn't interrupt service.
Concurrently maintainable
Infrastructure that can be maintained or repaired without shutting down IT operations.
BESS (Battery Energy Storage System)
Battery buffer smoothing renewable/grid supply and riding through short outages.
Captive solar
On-site or dedicated solar generation feeding the DC directly rather than drawing purely from the grid.
DG (diesel generator) backup
Last-resort backup power behind UPS/BESS, sized for extended grid outages.
Day-1 renewable integration
Designing renewable supply into the facility from initial commissioning, not retrofitted later.
ATS (Automatic Transfer Switch)
Seamlessly switches the power path to a backup source (battery/DG) on grid failure, without interrupting supply.
LFP (Lithium Iron Phosphate) battery
The battery chemistry used for hours-scale autonomous backup in NICPL's containerized-DC modules.
On-site substation / grid tie-in
A dedicated substation at each site that interconnects to the utility grid directly, rather than relying on a shared upstream service transformer — the deployment standard NICPL builds every site to.
GIS (Gas Insulated Switchgear)
Compact, sealed switchgear used at the on-site substation in place of older air-insulated designs — a smaller footprint with built-in smart automation.
TVP (Transient Voltage Protection) transformer
A transformer engineered to absorb grid-side surges and switching transients before they reach IT load.
SCADA (Supervisory Control and Data Acquisition)
Real-time digital monitoring and control across the power path, from the substation down to the rack — not just after-the-fact metering.
STATCOM (Static Synchronous Compensator)
Power-electronics equipment that stabilises voltage and power factor in real time, keeping power quality within tolerance under variable renewable and IT load.
Harmonic filters
Equipment that removes electrical harmonics generated by switching and IT load, protecting both the site and the upstream grid from power-quality issues.

Building & Civil

Built-up area
Total constructed floor area of the facility.
5MW modular block
The repeatable construction unit; four blocks make one 20MW site.
Mixed rack density zoning
Provisioning different areas of the same facility for the 5kW–25kW air-cooled band and the 25kW–135kW hybrid-cooling band on demand, avoiding stranded capacity.
Civil / seismic variability
How local soil capacity, seismic zone, and flood/groundwater conditions drive foundation and structural design per site.
ISO container / containerized DC
A 20ft or 40ft standard shipping-container form factor, factory-integrated with power, cooling, and IT before site delivery — used for rapid or space-constrained deployments.
FAT (Factory Acceptance Testing)
Witnessed testing of a fully assembled unit before it leaves the factory, verifying power, cooling, monitoring, fire, and security all perform to spec ahead of site delivery.
Sealed cable & pipe entry
Mechanical sealing at every cable and pipe penetration — the same barrier used for fire and water protection also closes off the entry points pests and rodents exploit.
IPM (Integrated Pest Management)
A pest-control approach that leads with inspection, monitoring, and sanitation, treating pesticide application as a last resort rather than a routine.
MMR (Meet-Me Room)
A neutral interconnection space where carriers and network providers physically cross-connect — standard on every NICPL site for telco and CDN customers.

Monitoring & Automation

IIoT (Industrial Internet of Things) sensor
A hardwired, network-connected sensor feeding environmental and equipment data straight into the facility monitoring platform — chosen over wireless for reliability, since there is no battery-replacement cycle or RF interference to manage in a mission-critical hall.
Environmental monitoring
Continuous, hardwired sensing of temperature, humidity, differential pressure, airflow, water leaks, vibration, door/access status, and air quality — at rack-level density, not room-level averages.
Differential pressure monitoring
Measuring pressure differences across aisle containment and underfloor plenum zones to catch air leaks before they show up as a hot spot.
DCIM (Data Center Infrastructure Management)
The unified software platform that brings rack power, environmental sensor data, UPS/battery health, and cooling/fire status together in one place — the alternative to a patchwork of disconnected point tools.

Certification

TIA-942 Rated-3
An open, ANSI-published data-center standard with third-party accredited certification, owned by the Telecommunications Industry Association (TIA) — not affiliated with NICPL. See the full TIA-942 vs Uptime comparison for detail.
Uptime Institute Tier III
A proprietary methodology owned and certified directly by Uptime Institute, LLC — not affiliated with NICPL. See the full TIA-942 vs Uptime comparison for detail.
Tier-3 certified facility vs. Tier-3 design
Constructed-facility certification verifies what was actually built, not just what was planned.
OCP Ready™ v1 Data Center Site
An Open Compute Project Foundation facility-readiness designation, assessed against a published requirements matrix covering data center access, IT technical space, electrical systems, cooling, and telecom cabling — confirming a facility supports open, vendor-neutral Open Rack deployments without rework. OCP Ready™ is a trademark of the Open Compute Project Foundation, which is not affiliated with, and does not endorse, NICPL.
IGBC Gold (or better)
Every NICPL building targets certification from the Indian Green Building Council (IGBC) at Gold level or higher — sustainable site planning, energy and water efficiency, and material selection assessed against a national green-building standard. IGBC is a registered trademark of the Indian Green Building Council / CII, which is not affiliated with, and does not endorse, NICPL.
MeitY empanelment
Ministry of Electronics and Information Technology (MeitY), Government of India, data center empanelment — the eligibility track for government and PSU workloads under India's data-localisation framework. MeitY is a government body, not affiliated with NICPL.
ISO/IEC 27001
Information Security Management System (ISMS) certification — the baseline standard for how information security risk is managed, published by the International Organization for Standardization (ISO), which is not affiliated with NICPL.
ISO/IEC 27017
Code of practice for information security controls specific to cloud and colocation services, published by the International Organization for Standardization (ISO), which is not affiliated with NICPL.
ISO/IEC 27018
Code of practice for protecting personally identifiable information (PII) in a cloud/colocation environment, published by the International Organization for Standardization (ISO), which is not affiliated with NICPL.
ISO/IEC 20000
IT Service Management (ITSM) standard, covering how IT services — including colocation operations — are delivered and supported, published by the International Organization for Standardization (ISO), which is not affiliated with NICPL.